A I R    C O N D I T I O N E R S
AIR COOLED DX SPLIT UNITS - AIR COOLED CONDENSING UNITS

 

38VT020/024 & 38VTA030

38VT020/024 & 38VTA030

Features

  • Hermetic rotary compressor
  • Built-in thermal overload protector against high current or temperature
  • Carrier lanced sine wave fin pattern - ensures high EER
  • Flare liquid and suction service valves ensure fast and easy installation and servicing


38VTA040/050/060

38VTA040/050/060

Features

  • Fully hermetic scroll compressor
  • Built-in thermal overload protector against high current or temperature
  • Carrier lanced sine wave fin pattern - ensures high EER
  • Flare liquid and suction service valves ensure fast and easy installation and servicing
  • Metal fan guard - offers quick access and easy maintenance with low noise characteristics
  • High/low pressure switches and crankcase heater ensure safety and long term reliability
  • Built-in solid-state anti-recycle 5 minutes timer


Specification

Model
38VT020
38VT024
38VTA030
38VTA040
38VTA050
38VTA060
Nominal Capacity (kW)*
5.27
7.03
8.79
10.6
14.1
17.6
Power Consumption (CDU) (kW)*
2.13
2.54
3.03
3.5
4.5
6.2
Refrigerant
R-22
Power Source (V-Ph-Hz) Nominal
230-1-50
380/420-3-50
CDU EER
-
11.2
11.5
11.7
Compressor
Type
Rotary
Fully Hermetic Scroll
LRA (A)
43/47
66/72
63/67
50
65.5
74
RLA (A)
9.5/9.4
11.9/11.3
12.2/12.5
7.9
10
Power Supply
230-1-50
380/420-3-50
Input kW @ 220V/240V
2.03/2.13
2.5/2.54
2.5/2.6
3.6
4.4
5.2
Oil Charge
430CC
1100CC
1130CC
Fan Motor
Type
Direct Driven
Output (kW)
0.06
0.14
0.175
Number
1
FLA (A)
0.6
0.63
1.46
Power Supply
230-1-50
Condenser Fan
Type
Draw-Thru
Number
1
Blade Diameter (mm)
405
609
Drive
Direct Driven
Condenser Coil
Rows-Fins (m)
2-591
Face Area (m²)
0.46
1.14
Dimensions
Width, W (mm)
340
432
Length, L (mm)
825
1130
Height, H (mm)
650
945
Connections
Type
Flare
Liquid (mm)
3/8"
Suction (mm)
5/8"
3/4"
Net Weight (kg)
55
57
86
96
98
External Finish
Alpine Mist
Sound Pressure Level (dBA)**
-
62
64
66
Protection Devices
Compressor Overload
Thermal Overload, Timer

FLA: Full Load Amps           LRA: Locked Rotor Amps           RLA: Rated Load Amps.
*   Data rated to JIS standard at 35°C (95°F) ambient 26.7°C/19.4°C (80°F/67°F) indoor condition when matched with Carrier approved fan coil units.